Abstract
The integration of district heating (DH) and cooling (DC) in the sustainable energy system of the future requires a significant reduction in operating temperatures. Supply temperatures below 70 °C are required for new 4th Generation DH. Main benefits are the use of low exergy heat sources and the reduction of heat losses. The reduction of heat losses is achieved by reducing the driving temperature difference between the medium pipe and the ground. The decrease of the return temperature level is limited by the consumer behaviour and the ground temperature level. As a consequence, the reduction of the supply temperature is accompanied by a reduction of the maximum transmittable heat flow. For energy efficiency and economic reasons, the relative heat losses are therefore an important design value for DH networks. The study proposes an approach to estimate the relative heat losses by using steady-state heat loss models and analyses the values for different DH generations. In particular, due to the rising of the near-surface soil temperature, the relative cold losses are also studied.
| Original language | English |
|---|---|
| Pages (from-to) | 479-490 |
| Number of pages | 12 |
| Journal | Environmental and Climate Technologies |
| Volume | 25 |
| Issue number | 1 |
| DOIs | |
| Publication status | Published - 4 Sept 2021 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 07 Affordable and Clean Energy
-
SDG 12 Responsible Consumption and Production
Keywords
- Cold losses
- district cooling
- district heating
- heat losses
Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver